Room Electrical Load Calculator

Estimates the simultaneous load and current in each room, with a suggested breaker rating and cable size to check against AS/NZS 3000.

A bedroom with a 1,500 W air conditioner, a 100 W TV and 80 W of LED lighting has 1,680 W connected. With a diversity factor of 0.8, the simultaneous load is 1,344 W, which draws about 6.5 A at 230 V with a power factor of 0.9. A 10 A breaker is the next standard rating above that current, and the cable should be sized to suit the breaker. This calculator runs the same steps for each room and returns the simultaneous power, current, breaker rating and cable size to check.

Australian homes are supplied with single-phase power at a nominal 230 V in every state and territory, so the arithmetic is the same whether the home is a brick veneer house in Sydney, a terrace in Melbourne, a Queenslander in Brisbane, a house-and-land package in Perth or a unit in Adelaide. What changes is the mix of loads. A room with a split system, a computer, a gaming console and a space heater carries far more connected load than a bedroom with a bedside lamp, so the diversity factor matters more in the first room than in the second.

The reason to apply a diversity factor, rather than adding up every appliance, is that not everything in a room runs at once. The current is what determines the breaker, and the breaker is what protects the cable from overheating. Use the calculator to check whether an existing circuit has room for another appliance, or to choose the breaker and cable for a new run. Then confirm the design with a licensed electrician before any work starts, because the calculator does not replace an inspection.

Work through each room separately, starting with the largest fixed loads and then adding the smaller ones. A room with several large appliances on one circuit may need a separate circuit even when the total looks acceptable, so the output is best read as a check on the circuit, not a replacement for a design.

The result updates automatically.

Selecting the type fills in typical values — adjust as needed.

Total of the light fittings installed. LED: 5–15 W/fitting; halogen: 35–50 W/fitting.

TV (~100 W), computer (~80 W), games console (~150 W), chargers, etc.

Air conditioning (~1,000–3,500 W), convector heater (~1,000–2,000 W), electric towel rail (~200–600 W).

Electric cooker (~6,000–7,000 W), oven (~2,000–3,500 W), washing machine (~2,000 W).

The percentage of appliances running at the same time. 80% is the typical value for a home.

Recommended breaker

10 A

Minimum rating for a current of 7.3 A

Simultaneous load

1,504 W

80% of 1,880 W installed

Total installed load
1,880 W
Lighting
80 W
Appliances / sockets
300 W
Heating / AC
1,500 W
Other appliances
0 W
Circuit current
7.3 A
Minimum cable size
1,5 mm²

Turn this calculation into a quote for your client

We're building a tool for professionals. Be among the first to try it.

Share

How it works

1

Select the room type. Typical loads fill in automatically.

2

Enter the lighting load, which is the sum of the installed or planned globes and LED fittings.

3

Enter the power of appliances plugged into power points, plus any heating or cooling systems.

Formula

I = (P_inst × DF) / (V × 0,9)
I — Circuit current (A)
P_inst — Total installed power (W) = lighting + appliances + heating + other
DF — Diversity factor as a decimal, typically 0.80 for a dwelling
V — Single-phase supply voltage in Australia: 230 V
0,9 — Power factor (cos φ) typical for domestic installations, 0.9

How the calculation works

How to work out the power needed for each room

Sizing an electrical circuit involves three variables: the connected load, the share of that load that runs at the same time, and the supply voltage. Getting any one of them wrong leaves the circuit in one of two states. If it is undersized, the breaker trips during normal use. If the breaker is oversized for the cable, the cable can carry more current than it is rated for and overheat, which is the more dangerous outcome because nothing trips to stop it.

Australian homes are supplied with single-phase power at a nominal 230 V and 50 Hz, so the formula needs no regional adjustment between states and territories. Domestic loads are a mix of resistive, electronic and motor loads, so the power factor is not one fixed value. The calculator uses 0.9 as a practical planning figure, not a measurement of your home.

The formula and the diversity factor

The current in a circuit follows from the active power and the voltage: I = P / (V × cos φ). The calculator applies that relationship to the simultaneous power rather than the total installed power, using I = (P_inst × DF) / (V × 0.9).

P_inst is the total installed power in watts, made up of lighting, appliances, heating and any other fixed loads. DF is the diversity factor, the share of that load expected to run at the same time. Take a room with 2,000 W installed and a diversity factor of 0.8. The simultaneous power is 1,600 W, and the current is 1,600 divided by (230 × 0.9), or about 7.7 A. That current, not the sum of every appliance, is what sets the breaker.

The default of 0.8 suits general use in a dwelling, where people rarely run every appliance at once. Fixed appliances that run for long periods, such as an electric cooktop, a hot water system or a ducted heater, can reach full power for hours. For those loads, use 1.0. Using 1.0 for the whole room is the more conservative choice when you do not know how lightly it is used.

Standard breaker ratings

Miniature circuit breakers come in standard ratings. The common ones are 6, 10, 16, 20, 25, 32, 40, 50 and 63 A. The breaker is the next rating above the calculated current. A calculated current of 9.5 A needs a 10 A breaker. A calculated current of 17.3 A needs a 20 A breaker, because a 16 A breaker would trip at that load.

Breaker curves matter as well. Curve B breakers suit steady resistive loads such as lighting and heating. Curve C breakers suit motors and equipment with a high start-up current, such as air conditioners, washing machines and fridges. The curve and rating definitions are set out in AS/NZS 60898.1, the Australian and New Zealand standard for circuit-breakers in household and similar installations. The calculator returns the rating only. Choosing the curve is part of the electrician's design work.

Cable size: the rule that is easy to overlook

The cable is not a separate decision from the breaker. It is the condition that keeps the circuit safe. The cable must carry the breaker's rating continuously without overheating, so the breaker has to be matched to the cable. A 25 A breaker on a cable rated for 16 A switches off too late to protect it, because the breaker only trips at its own rating, and the cable can reach a dangerous temperature before that happens.

Cable current ratings depend on installation conditions as well as conductor size. A cable run inside insulation, grouped with other cables or installed in a hot ceiling space carries less current than the same cable in free air. The current-carrying tables in AS/NZS 3000 and the cable selection standards it refers to set those values. Use them, or ask a licensed electrician to, rather than relying on a single figure from a summary like this one.

In many Australian houses, lighting is wired in 1.5 mm² cable and general power in 2.5 mm² cable. That is common practice, not a rule for every job, so each circuit should be checked against its own conditions. Air conditioners, electric cooktops and hot water systems usually need heavier cable and a higher-rated breaker, which is why they normally sit on dedicated circuits.

Common wiring mistakes in Australian homes

Plugging a fixed high-load appliance into a power point. An air conditioner with a 1,500 W input draws roughly 7 A at 230 V before the television and lights are counted. A general power point on a shared circuit is not meant for a continuous high load. Air conditioners and similar appliances should sit on a dedicated circuit with the correct breaker and cable.

Relying on power boards as a permanent fix. Power boards and extension leads have a maximum current rating, and they heat up when they carry a load close to that limit for long periods. Chaining several boards together, or running a permanent heater from one, creates a fire risk that grows over time. The heat degrades insulation gradually, so the problem is not always obvious.

Ignoring start-up current. Motors in air conditioners, washing machines and fridges draw a surge several times their running current when they start. A circuit that handles the steady load can still trip on that surge if the breaker curve is wrong, or the surge can overload a circuit that other appliances are already drawing from. Curve C breakers handle these surges better than curve B breakers, as the curve definitions in AS/NZS 60898.1 reflect.

Assuming the circuit is safe because the breaker has not tripped. A breaker protects the cable against overload and short circuit. It does not confirm that the wiring is in good condition, that the earthing is correct or that the circuit has residual current device protection. Under AS/NZS 3000, most general power circuits must be protected by an RCD. A switchboard that has been altered should be checked by a licensed electrician.

What this calculator does not check

The calculator estimates loads for planning and for checking an existing circuit. It does not check voltage drop over long cable runs, earthing, cable grouping, ambient temperature, protection coordination in the switchboard or the rating of the main supply. Those checks are part of a proper design under AS/NZS 3000 and belong to a licensed electrician. Treat the result as the starting point for that conversation, not the end of it.

When to bring in a licensed electrician

Any change to the switchboard, new circuits, altered wiring or replacement of power points needs a licensed electrician. Licensing and certification are handled at state and territory level, and the rules differ between them. In Victoria, for example, Energy Safe Victoria, the state electrical safety regulator, licenses electrical workers. The Electricity Safety Act 1998 requires a licensed electrician to issue a Certificate of Electrical Safety for new or altered electrical installation work, and that certificate should be kept with the home records. Other states and territories have their own regulators and certification arrangements, so check the rules that apply where the home is located. Homeowners can usually handle small tasks such as replacing a light globe or resetting a tripped breaker. Anything beyond that should be checked against those rules before work starts.

Frequently asked questions

What is the maximum load on a single power point in Australia?

A power point's rating and the circuit breaker both limit how much load it can carry, but the breaker protects the whole circuit rather than one outlet. A 2,400 W kettle draws about 10.4 A at 230 V on its own, so it should not share a circuit with a heater or another high-load appliance. Appliances that run for long periods, such as electric cooktops, hot water systems and large heaters, belong on a dedicated circuit wired to AS/NZS 3000, not on a general power point. Power boards and extension leads are not a substitute for a properly installed outlet.

What breaker do I need for a bedroom with an air conditioner?

It depends on the rated input of the unit, which is on its label, and on the other loads in the room. Take a 1,500 W air conditioner, a 100 W TV and 80 W of LED lighting. With a diversity factor of 0.8 and a power factor of 0.9, the simultaneous current is about 6.5 A, so a 10 A breaker is the next standard rating above it. Add a 2,000 W panel heater to the same circuit and the current rises to about 14.2 A, which moves the minimum breaker to 16 A and means the cable must be checked again.

What is the diversity factor and why does it matter?

The diversity factor is the share of connected load that runs at the same time. A room with 3,000 W connected and a factor of 0.8 has a simultaneous load of 2,400 W, which lowers the breaker and cable size needed. This calculator uses 0.8 as the default for dwellings. For fixed appliances that run for long periods, such as an electric cooktop or a hot water system, use 1.0, because those loads can run at full power for hours. A factor lower than the real use of the room can leave a circuit undersized, so when in doubt, use a higher value.

What cable size should I use with a 16 A circuit breaker?

The cable must carry the breaker's rating continuously without overheating, so the breaker has to protect the cable, not the other way round. The cable size comes from the current-carrying capacity tables in AS/NZS 3000 and the cable selection standards it refers to. Those values depend on how the cable is installed, whether it runs inside insulation, and how many cables are grouped together. Fitting a 25 A breaker to a cable rated for less removes the protection, because the breaker will not trip before the cable overheats. Have a licensed electrician confirm the size for the actual installation.

Can I add more appliances to an existing circuit?

Yes, as long as the total current stays within the breaker rating under normal use. A 16 A circuit carries roughly 3,300 W at 230 V with a power factor of 0.9. If the circuit already supplies 2,000 W of appliances, you can add about 1,300 W before reaching that limit. Check the start-up surge as well as the running load. Motors in air conditioners, washing machines and fridges draw several times their running current when they start, so a circuit that looks fine on paper can still trip. Under AS/NZS 60898.1, a breaker with a C curve tolerates those surges better than one with a B curve.

When do I need a licensed electrician in Australia?

Most electrical work in a home needs a licensed electrician, and the licensing rules are set by each state and territory. Work on a switchboard, new circuits, changes to existing wiring and replacement of power points generally needs one. Replacing a light globe or resetting a tripped breaker are tasks most homeowners can handle. In Victoria, Energy Safe Victoria administers electrical licensing, and the Electricity Safety Act 1998 requires a licensed electrician to issue a Certificate of Electrical Safety for new or altered work. Keep that certificate with your home records. For the rules that apply to your job, check the electrical safety regulator for your state or territory.

View all Renovation & Systems calculators →

By RivoCalc · Reviewed under our editorial methodology · Updated 12 May 2026

This calculator gives an estimate for planning and checking purposes only. Real loads, diversity, cable runs, ambient temperature and cable grouping all change the result. Installation, alteration or replacement of switchboards and circuits must be carried out by a licensed electrician, and all designs must comply with AS/NZS 3000 and the electrical rules of your state or territory.