Solar Battery Size Calculator (kWh)

Estimate the solar battery capacity your home needs in kWh, with LiFePO4, NMC and lead-acid chemistries and a degradation margin.

A home that uses 8 kWh of electricity a day and plans for one day of autonomy needs a LiFePO4 battery with a recommended capacity of about 10.8 kWh. Before the 15% degradation margin is added, the minimum nominal capacity is about 9.4 kWh.

That result comes straight from the calculator's formula: daily consumption multiplied by the days of autonomy, divided by depth of discharge and round-trip efficiency, then increased by a margin for ageing. It is a planning estimate, and the rest of this page explains each input so you can judge whether the figure fits your own household.

Picture a semi-detached house in Manchester with solar panels on the roof. The panels generate during daylight, but many households use a large share of their electricity in the evening and overnight. A battery stores the surplus produced during the day and releases it when the panels are not producing. Sized well, it avoids two opposite mistakes. A battery that is too small wastes surplus generation, while one that is too large ties up capital that never earns back its cost.

The calculator asks for four inputs: daily consumption in kWh, days of autonomy, battery chemistry and, optionally, the price per kWh from an installer's quote. It then shows the minimum nominal capacity and the recommended capacity with margin. For planning, use the recommended figure, then compare it with the module sizes an installer can supply, rounding up to the nearest one.

Treat the output as a pre-sizing estimate. Real consumption, the usable capacity of the battery and the limits of the inverter all affect the final design, and a qualified installer will check them against your household's electricity use.

The explanation below uses metric units; the calculator works in either system.

The result updates automatically.

1-bed home: 4–6 kWh/day · 2-bed: 6–8 kWh/day · 3-bed: 8–12 kWh/day · House: 10–20 kWh/day

Grid-connected: 1 day · Off-grid or areas with outages: 2–3 days

LiFePO4 is the most recommended for homes: longer life and safer.

Enter the price from the installer's quote to estimate the total cost.

Recommended capacity

10.8kWh

includes a 15% margin for degradation over its lifespan

Usable energy needed
8.0 kWh
Minimum nominal capacity
9.4 kWh
Depth of discharge (DoD)
90%
Round-trip efficiency
95%
Share

How it works

1

Enter your daily household consumption in kWh. Find it on your electricity bill by dividing the monthly consumption by 30.

2

Set the days of autonomy you want the battery to cover. Use one day for grid-connected systems, and two to three days for areas with frequent power cuts or for off-grid homes.

3

Select the battery chemistry. LiFePO4 is a common choice for new home installations.

Formula

C = (E × N) / (DoD × η) × (1 + m)
C — Recommended battery capacity (kWh)
E — Daily electricity consumption (kWh/day)
N — Days of autonomy
DoD — Depth of discharge, calculator defaults: LiFePO4 = 0.90, NMC = 0.80, lead-acid = 0.50
η — Round-trip efficiency, calculator defaults: LiFePO4 = 0.95, NMC = 0.93, lead-acid = 0.85
m — Degradation margin (0.15 = 15%)

How the calculation works

Solar Battery Size: How Many kWh Do You Need?

Solar panels produce most of their electricity in daylight, and none at night. A battery fills that gap. It stores surplus generation from the day and releases it when the panels are not producing, in the evening, overnight or during a dull spell. Sizing it correctly avoids two opposite errors. A battery that is too small leaves surplus energy unused, while one that is too large represents capital that never earns back its cost.

How the sizing formula works

The formula starts from two figures: the household's daily electricity consumption in kWh, and the number of days of autonomy. Autonomy is how many consecutive days without sun the battery should cover on its own. Multiplying the two gives the energy the battery must deliver.

The battery cannot deliver all of its rated capacity, for two reasons. The first is depth of discharge (DoD), the share of capacity that can be used without shortening the battery's life. The second is round-trip efficiency (η), the share of the energy put into the battery that comes back out after a full charge and discharge cycle, with the rest lost as heat and in conversion. Dividing the energy requirement by DoD and efficiency gives the nominal capacity needed.

The final term, (1 + m), adds a margin for degradation. The calculator uses 15% by default. This is a planning allowance rather than a measured figure, and it keeps the system able to cover winter nights after the battery has aged.

Worked example: a home that uses 8 kWh a day, with one day of autonomy and LiFePO4 chemistry, has an energy requirement of 8 × 1 = 8 kWh. Dividing by 0.90 × 0.95 (0.855) gives 9.4 kWh of nominal capacity. Multiplying by 1.15 gives a recommended capacity of 10.8 kWh.

Battery chemistries on the UK market

Three chemistries account for most home battery systems. Each one has different defaults in the calculator, and those defaults change the size needed for the same household.

LiFePO4 (lithium iron phosphate) is a common choice for new home installations. The calculator assumes a DoD of 0.90 and an efficiency of 0.95 for it, the most favourable values of the three. It is generally regarded as having a longer cycle life and better thermal stability than other lithium chemistries, which is why it is often preferred where safety and longevity matter. Its main drawback is a higher upfront cost.

NMC (nickel manganese cobalt) offers high energy density, which allows compact units. The calculator assumes a DoD of 0.80 and an efficiency of 0.93, so the same daily use needs a somewhat larger nominal capacity than with LiFePO4. NMC suits installations where space is the main constraint.

Lead-acid (VRLA or AGM) is the oldest of the three. It is usually the cheapest option per kWh of nameplate capacity, but the calculator assumes only a DoD of 0.50 and an efficiency of 0.85. For the same usable energy, a lead-acid system needs about twice the nameplate capacity of a LiFePO4 system, since the combined DoD and efficiency factor is 0.425 against 0.855. It is mainly considered for off-grid sites where the upfront cost matters most.

Autonomy: one day or more?

For grid-connected systems, one day of autonomy is a common planning choice. The battery's job is to store the day's surplus and use it in the evening and overnight, because the grid covers longer periods without sun.

Off-grid systems, and homes in rural areas with frequent power cuts, are normally designed for two to three days. Homes in cloudier regions, where generation drops sharply in winter, may need to plan for more days than the same home in a sunnier location. Some designers add a fraction of a day for the darkest months rather than design for several full days.

Common sizing mistakes

The most frequent mistake is to size the battery for total daily consumption without considering the energy used directly while the sun is shining. The calculator uses total consumption, so for a home with a lot of daytime use it gives an upper estimate. Suppose a home uses 8 kWh a day, but 4 kWh of that is used directly during daylight by a washing machine, a cooker or a computer. Only the remaining 4 kWh needs storing for night use. A 9.4 kWh nominal battery in that case would be only about half used.

The second mistake is to ignore degradation. Lithium batteries lose capacity gradually with cycling and age, so a system sized exactly for today's needs may fall short in later years, particularly in winter. The 15% margin is there to absorb that gradual loss, but it is an allowance, not a guarantee. Check the warranty terms for guaranteed capacity retention, and compare them with the number of cycles you expect each year.

In practice, installers round the calculated figure up to the nearest module size they can supply. If the calculation gives 10.8 kWh, a 10 kWh system made of two 5 kWh modules falls just short, so a larger configuration would be chosen instead. Compatibility with the inverter often decides the final choice, because not every inverter works with every battery voltage and chemistry.

A third mistake is to treat the result as a guarantee of backup power. The calculator sizes a battery for a planned pattern of use. A battery cannot be expected to power every appliance through a long outage unless the system is designed for that load.

Installation rules in the UK

A battery is part of an electrical installation, so the work falls under the Building Regulations and the wiring standard BS 7671. In England and Wales, Part P of the Building Regulations covers electrical work in dwellings. In Scotland, Building Standards apply instead. The battery's own safety should be assessed against BS EN IEC 62619, the safety standard for lithium secondary batteries used in industrial and stationary applications.

Connecting a battery to a solar system and to the grid requires notification or approval under the Energy Networks Association's engineering recommendations: G98 for smaller systems and G99 for larger ones. The distribution network operator for your area must be informed before the system is connected. Installers certified under the Microgeneration Certification Scheme (MCS) work to these requirements as part of their normal process.

When to use this estimate, and when not to

Use the calculator to compare options and to understand what drives the size of a battery. Do not treat its output as a final design. It does not model the hourly profile of your household, the seasonal output of your panels, your tariff structure, or the charge and discharge limits of your inverter.

For a final design, an installer should measure consumption hour by hour rather than relying on a daily total, check the battery's compatibility with the inverter and inspect the existing electrical installation, including the consumer unit. Off-grid systems, which need a full energy balance over a whole year and often a backup generator, go beyond what this calculator is designed to do.

Frequently asked questions

What size battery does a three-bed house need in the UK?

It depends on daily use and the number of days of autonomy. A three-bed house that uses 8 kWh a day, with one day of autonomy and LiFePO4 chemistry, needs a recommended capacity of about 10.8 kWh. If the same house uses 10 kWh a day, the recommended capacity rises to about 13.5 kWh. Check your own consumption on your electricity bill before choosing a size, because the number of occupants and the appliances in use change the result far more than the number of bedrooms does.

What is the difference between LiFePO4 and NMC batteries?

LiFePO4 is the chemistry the calculator treats most favourably in terms of usable energy. Its default depth of discharge is 0.90, against 0.80 for NMC, and its default round-trip efficiency is 0.95, against 0.93. LiFePO4 is generally regarded as having a longer cycle life and better thermal stability. NMC has a higher energy density, which allows more compact units, but it tends to suit homes where space is the main constraint. For most new domestic installations, LiFePO4 is the more common recommendation.

What is depth of discharge (DoD) in a home battery?

Depth of discharge is the share of a battery's rated capacity that can be used without shortening its life. A 10 kWh battery with a DoD of 0.90 provides 9 kWh of usable energy. A lead-acid battery with a DoD of 0.50 provides only 5 kWh from the same 10 kWh rating, so it needs twice the nameplate capacity to deliver the same usable energy. The calculator uses the values shown in the formula legend, and you should confirm the figures in the datasheet for the specific battery you are considering.

Can I add more battery modules later?

Many modular home batteries allow additional modules to be connected to increase capacity. Before buying, check the maximum battery capacity your inverter supports, and confirm that the inverter accepts the battery voltage and chemistry you intend to use. Some inverters cannot work with large battery banks without extra hardware. Planning for expansion at the start avoids replacing the inverter later if your consumption grows, for example after adding an electric heat pump or an electric vehicle charger.

How long does a home battery last?

Lifespan depends on the battery chemistry, the operating temperature, the depth of discharge and how many cycles the battery completes each day. Daily cycling wears a battery faster than occasional use, and a battery that is regularly fully discharged will age sooner. The calculator does not estimate lifespan. Warranties usually state the capacity the manufacturer guarantees after a set number of cycles or years, and those terms are the most reliable guide for planning.

Do I need a certified installer to fit a home battery in the UK?

In most cases, yes. Electrical work in homes in England and Wales must meet Part P of the Building Regulations, and Building Standards apply in Scotland. The wiring must comply with BS 7671. Connecting the battery to the grid also requires notification or approval under Energy Networks Association recommendation G98 for smaller systems or G99 for larger ones, and your distribution network operator must be informed. An installer certified under the Microgeneration Certification Scheme (MCS) is the practical route to meeting these requirements.

Related calculators

View all Climate & Energy calculators →

By RivoCalc · Reviewed under our editorial methodology · Updated 16 June 2026

This calculator gives an estimate for pre-sizing only. Real consumption depends on equipment, climate, occupancy and how the household uses electricity, and usable battery capacity changes with temperature and age. Confirm the design with a qualified installer, and check the battery against the inverter's specification before buying.