Room Electrical Load and Circuit Current Calculator

Estimates the simultaneous load and circuit current for each room, with the MCB rating and cable size to check against Irish wiring rules.

A bedroom with a 1,500 W air conditioning unit, a 200 W television and two 60 W device chargers has 1,820 W installed. With a simultaneity factor of 0.8, the load running at the same time is 1,456 W, or about 7.0 A at 230 V with a power factor of 0.9. For that circuit, a 10 A device is the next standard rating up, with a cable sized to match it under the installation method used.

If the same bedroom also has a 300 W desktop computer, the simultaneous load rises to 1,696 W, or about 8.2 A. That still fits a 10 A device, but there is little margin left, so anything else added to the circuit needs checking first.

This calculator applies the design logic of I.S. 10101, the Irish national rules for electrical installations, which follow the international IEC 60364 series of wiring standards. For each room it returns the simultaneous power, the circuit current, a suggested protective device rating and a starting cable size. The figures are a planning tool. They feed into a design that a registered electrical contractor then checks against the installation method, the cable routes and the rules for dwellings in Part P of the Building Regulations.

The calculator suits three situations. A homeowner renovating a semi-detached house in the Dublin suburbs can see whether an existing circuit has room for a new appliance. A tenant or landlord with a terrace in Cork can check a load before buying equipment for it. A contractor can use it for a quick first estimate before the detailed design. It is not a substitute for that design, and it does not replace the work of a registered electrical contractor on any real installation.

The result updates automatically.

Selecting the type fills in typical values — adjust as needed.

Total of the light fittings installed. LED: 5–15 W/fitting; halogen: 35–50 W/fitting.

TV (~100 W), computer (~80 W), games console (~150 W), chargers, etc.

Air conditioning (~1,000–3,500 W), convector heater (~1,000–2,000 W), electric towel rail (~200–600 W).

Electric cooker (~6,000–7,000 W), oven (~2,000–3,500 W), washing machine (~2,000 W).

The percentage of appliances running at the same time. 80% is the typical value for a home.

Recommended breaker

10 A

Minimum rating for a current of 7.3 A

Simultaneous load

1,504 W

80% of 1,880 W installed

Total installed load
1,880 W
Lighting
80 W
Appliances / sockets
300 W
Heating / AC
1,500 W
Other appliances
0 W
Circuit current
7.3 A
Minimum cable size
1,5 mm²

Turn this calculation into a quote for your client

We're building a tool for professionals. Be among the first to try it.

Share

How it works

1

Select the room type. Typical values fill in automatically.

2

Adjust the lighting power to the sum of the lamps installed or planned.

3

Enter the power of the appliances on the sockets and of any heating or cooling systems.

Formula

I = (P_inst × sf) / (V × 0,9)
I — Circuit current (A)
P_inst — Total installed power (W) = lighting + appliances + heating + other
sf — Simultaneity factor (decimal); the calculator defaults to 0.80 for dwellings
V — Single-phase supply voltage in Ireland, 230 V
0,9 — Power factor (cos φ) for domestic installations, fixed at 0.9 (written 0,9 in the formula)

How the calculation works

How to work out the electrical load for each room

Sizing a circuit correctly comes down to three inputs: the installed power, the simultaneity factor and the supply voltage. Get any one of them wrong and the circuit ends up in one of two bad states. It is either undersized, so the protective device trips during normal use, or oversized, so it allows more current than the cable can safely carry, which leads to overheating over time.

In Ireland the supply is single-phase at 230 V and 50 Hz, the same nominal values used across most of Europe. The power factor (cos φ) is below 1 because many domestic loads, such as motors in fridges and washing machines and the electronic power supplies in televisions and chargers, do not draw current exactly in step with the voltage. The actual value depends on the equipment. This calculator uses 0.9 as a simplifying assumption, so that the result can be checked by hand.

The formula and the simultaneity factor

The current in a single-phase circuit follows from the power equation: I = P / (V × cos φ). The power that matters is not the sum of every appliance in the room. It is the power of the appliances that will be on at the same time, which is the simultaneous load.

The simultaneity factor (sf) captures that difference. A room with 2,000 W installed and a factor of 0.8 has a simultaneous load of 1,600 W. The resulting current, 1,600 / (230 × 0.9), is about 7.7 A, and that is the number that drives the choice of protective device. The calculator defaults to 0.8 for general socket and lighting circuits, and a designer should be able to justify any other value.

Fixed appliances that run for long periods at close to full power, such as electric showers, storage heaters or a cooker, should not be treated with the same factor. A factor of 1.0 is the safer choice for these loads, because they can draw their maximum power for hours at a time. The calculator lets you change the factor so that the choice is made deliberately.

Standard protective device ratings and what they mean

Miniature circuit breakers (MCBs) built to the EN 60898-1 product standard, adopted in Ireland as I.S. EN 60898-1, come in standard ratings of 6, 10, 16, 20, 25, 32, 40, 50 and 63 A. The device chosen is the next rating above the calculated current. A circuit with a current of 9.5 A needs a 10 A device. A current of 17.3 A requires at least a 20 A device.

For a typical semi-detached house in the Dublin suburbs, a bedroom with a 1,800 W air conditioning unit, a 100 W television, an 80 W computer and 60 W of LED lighting totals 2,040 W installed. With a factor of 0.8, the calculation is (2,040 × 0.8) / (230 × 0.9), which gives about 7.9 A. A 10 A device is enough. If a 2,000 W convector heater is added on the same circuit, the current rises to about 15.6 A, which means a 16 A device and a review of the existing circuit.

MCB curves matter as well. Type B devices suit resistive loads and lighting. Type C devices are used for motors, compressors and equipment with high starting currents, such as air conditioning and washing machines. Both types follow the same IEC 60898 series, so the rating and the curve must both be chosen.

Cable size and protection working together

The cable is not independent of the protective device. It is the part that must be protected. The basic principle in the Irish wiring rules is that the current-carrying capacity of the cable, under the actual installation method, must be at least equal to the rating of the device protecting it. If a 25 A device protects a cable that can only carry less current under its installation conditions, the device will not operate before the cable overheats. Protection is lost, even though the breaker looks correct on the consumer unit.

The cable size therefore depends on three things: the device rating, the installation method (clipped direct, in conduit, buried or in an insulated wall, for example) and the grouping and ambient temperature. The current-carrying capacity tables in I.S. 10101 give the values for each case. This calculator suggests a cable size as a starting point, but the table for the actual installation method must be checked before any cable is bought or pulled.

Higher-current loads, such as a cooker, an electric shower or an immersion heater, usually have their own dedicated circuit with a suitable cable and device. Sharing a general socket circuit with these loads is a common cause of trips and overheating.

Common mistakes in domestic installations

Plugging an air conditioning unit into a general socket. A 3.5 kW split unit draws roughly 15 to 17 A at 230 V on its own, which is close to the limit of a 16 A circuit. It should have a dedicated circuit with suitable protection and cable, not share a socket circuit with other loads.

Using extension leads as a permanent fix. Domestic extension leads are designed for temporary use. A lightweight lead that carries a heater and a hob for long periods overheats, and the heat degrades the insulation gradually. The problem is not immediate, but the fire risk grows over time.

Ignoring starting current. Motors in washing machines, air conditioning units and fridges draw several times their running current for a short moment at start-up. Type C devices are designed to tolerate these peaks, while Type B devices may trip even when the continuous current is within limits.

Adding loads without rechecking the circuit. Each new appliance changes the simultaneous load on its circuit. The calculation should be repeated whenever a load is added, moved or upgraded.

Edge cases

If the installed power is zero, the current is zero. If the simultaneity factor is set to 1.0, the result is the worst case for that room. A single appliance on its own circuit can draw its full rated power, so a factor of 1.0 is the safer choice in that case. Negative values are not meaningful for power and should be treated as data entry errors.

When to use this calculator, and when not to

Use it to estimate loads before buying equipment, to check whether an existing circuit has margin for a new appliance, or to produce a first-pass sizing for discussion with an electrician. Do not use it as the basis for a new installation, a change to the consumer unit, or any work where the cable, device and earthing must be designed and certified. The result also does not account for voltage drop over long cable runs, ambient temperature or grouping, which are all part of a full design.

When to call a registered electrical contractor

Work on fixed electrical installations in a dwelling is covered by Part P of the Building Regulations. Notifiable work, such as adding new circuits, changing a consumer unit or altering existing wiring, must be carried out by a registered electrical contractor who certifies the work on completion. Minor work, such as replacing a socket face plate, may not need notification, but the contractor or the local building control office can confirm which category a job falls into. The wiring rules themselves are set out in I.S. 10101, which the contractor applies to the design and the testing.

The calculator gives a reasoned estimate built on the standard design method. The final design belongs to a registered electrical contractor who can see the installation, check the actual cable routes and confirm the protective devices against the current rules.

Frequently asked questions

What is the most a standard Irish socket outlet can supply?

A standard Irish socket outlet is fed through a fused 13 A plug, so its practical limit is 13 A. At 230 V, that is about 2,990 W at a power factor of 1.0, and a little less at typical domestic power factors. Appliances that draw more than this, such as cookers, electric showers or immersion heaters, need a dedicated circuit with its own protection, as set out in I.S. 10101. Plugging a high-power heater into a socket outlet on a general circuit causes repeated trips, overheated plugs and, over time, damage to the cable and the socket.

Which MCB do I need for a bedroom with an air conditioning unit?

It depends on the rated input power on the unit's data plate, not on its cooling capacity. Take the unit's power, add the television, computer and lighting, multiply by the simultaneity factor of 0.8, then divide by 230 V times 0.9. For a bedroom with a 1,500 W air conditioning unit, a 100 W television and 80 W of lighting, the simultaneous load is 1,344 W, which gives about 6.5 A and a 10 A device. If a 2,000 W convector heater is also on the same circuit, the current rises to about 14.2 A, so the device must move to 16 A. The cable, the circuit and the installation method must then be checked against I.S. 10101 before anything changes.

What is the simultaneity factor and how does it change the design?

The simultaneity factor is the share of the installed load that runs at the same time. A room with 3,000 W installed and a factor of 0.8 has a simultaneous load of 2,400 W, which lowers the current, the device rating and the cable size the design needs. The calculator defaults to 0.8 for general circuits, and that value should be justified for the actual use. Fixed appliances that run at full power for long periods, such as electric showers, storage heaters or a cooker, should be treated at 1.0, because they can draw their maximum power for hours. A factor of 1.0 is the conservative choice when in doubt.

What cable size should I use on a general socket circuit?

There is no single answer, because the cable size depends on the device protecting it and on the installation method. The basic rule in I.S. 10101 is that the cable's current-carrying capacity, under the actual installation conditions, must be at least equal to the rating of the protective device. Sizes are read from the current-carrying capacity tables for the method used, which take account of clipped direct, conduit, buried cable, grouping and ambient temperature. The calculator gives a starting suggestion, but the final choice should be checked against those tables before any cable is bought or installed.

When do I need a registered electrical contractor in Ireland?

Work on fixed electrical installations in a dwelling is covered by Part P of the Building Regulations. Notifiable work, such as adding new circuits, changing a consumer unit or altering the existing wiring, must be carried out by a registered electrical contractor who certifies the work on completion and notifies it to the building control authority. Some minor works, such as replacing a socket face plate or a light switch, may not need notification. The contractor or the local building control office can confirm which category a job falls into before any work starts.

Is this result enough to design a circuit on its own?

No. The calculator estimates the simultaneous load and the protective device rating, which is the first step of a design. A full design also looks at voltage drop over long cable runs, the installation method, ambient temperature and grouping, earthing and RCD protection, the starting current of motor loads and the coordination between devices. The estimate is useful for planning and for spotting an overloaded circuit, but it is not a certified design. For any new circuit or change to the consumer unit, a registered electrical contractor should carry out the full design.

View all Renovation & Systems calculators →

By RivoCalc · Reviewed under our editorial methodology · Updated 12 May 2026

This calculator gives estimates only. Real current depends on the equipment, how it is used, its starting current and the installation conditions, so results may differ from the actual load. It does not replace a design or inspection by a registered electrical contractor, and it should not be used to select cable or protective devices for an installation without that check.