Electrical Load per Room Calculator
Works out the simultaneous load, current and breaker rating for each room, with a suggested cable size to check against AS/NZS 3000.
A bedroom with a 1,500 W heat pump air conditioner, a 200 W television and two 60 W chargers has 1,820 W installed. With a simultaneity factor of 0.8, the simultaneous load is 1,456 W, or 7.0 A at 230 V with a power factor of 0.9. On that circuit, a 10 A breaker is the next standard rating up. If the same bedroom also has a 300 W computer, the simultaneous load rises to 1,696 W (8.2 A). That still fits a 10 A breaker, but with little margin.
This kind of check applies in any New Zealand home, from a weatherboard house in Auckland to a townhouse in Wellington or a rebuild in Christchurch. Each room is treated as its own group of loads, because the air conditioner, lights and power points in a bedroom are rarely all running at full rating at the same time. The calculator adds up the installed power for each room, applies a simultaneity factor, and converts the result into a current in amps. The breaker rating and the cable size then follow from that current.
The simultaneity factor is a planning assumption, not a measurement. The 0.8 default suits general housing, and the power factor of 0.9 is a planning assumption rather than a measured value. Neither replaces the design method in AS/NZS 3000:2018, the Wiring Rules. Use the result to compare rooms, spot circuits that are close to their limit, and decide which ones a registered electrician should look at more closely.
Supply is assumed to be single-phase at a nominal 230 V and 50 Hz. Regulation 28 of the Electricity (Safety) Regulations 2010 sets the nominal single-phase voltage at 230 V, and WorkSafe New Zealand states the mains supply as 230 V, 50 Hz. Enter each room's installed power in watts, choose the simultaneity factor, and read the current. Once you have a figure, confirm the breaker and cable size with a registered electrician before any work begins, and keep the result as a planning note rather than a specification.
The result updates automatically.
Selecting the type fills in typical values — adjust as needed.
Total of the light fittings installed. LED: 5–15 W/fitting; halogen: 35–50 W/fitting.
TV (~100 W), computer (~80 W), games console (~150 W), chargers, etc.
Air conditioning (~1,000–3,500 W), convector heater (~1,000–2,000 W), electric towel rail (~200–600 W).
Electric cooker (~6,000–7,000 W), oven (~2,000–3,500 W), washing machine (~2,000 W).
The percentage of appliances running at the same time. 80% is the typical value for a home.
Recommended breaker
Minimum rating for a current of 7.3 A
Simultaneous load
80% of 1,880 W installed
- Total installed load
- 1,880 W
- Lighting
- 80 W
- Appliances / sockets
- 300 W
- Heating / AC
- 1,500 W
- Other appliances
- 0 W
- Circuit current
- 7.3 A
- Minimum cable size
- 1,5 mm²
How it works
Formula
How the calculation works
How to calculate the electrical load per room
Sizing an electrical circuit involves three variables: the installed power, the simultaneity factor and the supply voltage. Getting one of them wrong produces one of two problems. A circuit that is undersized trips during normal use, which is inconvenient but at least visible. A circuit that is oversized allows more current than its cable can safely carry, which risks overheating with no visible warning. The calculator works through all three variables in the same order for every room, so the results can be compared.
New Zealand's single-phase supply is nominally 230 V at 50 Hz. Regulation 28 of the Electricity (Safety) Regulations 2010 sets the nominal single-phase voltage at 230 V, and WorkSafe New Zealand states the mains supply as 230 V, 50 Hz, so those are the values the calculator uses. The power factor (cos φ) describes how much of the current does useful work. Mixed domestic loads, especially those with motors or electronic power supplies, draw some reactive current, so their power factor sits below 1. The calculator uses 0.9 as a planning value.
The formula and the simultaneity factor
The calculator applies the formula shown above. Current is the installed power, multiplied by the simultaneity factor, and divided by the supply voltage and a power factor of 0.9.
Installed power (P_inst) is the total of everything connected to the circuit: lighting, appliances on the power points, heating or cooling equipment and any other fixed loads. Not all of it runs at once. The simultaneity factor (sf) is the share of that installed power that is likely to run together. A room with 2,000 W installed and a factor of 0.8 has a simultaneous demand of 1,600 W. The current is then 1,600 / (230 × 0.9), or about 7.7 A, and that current is what sets the breaker.
The 0.8 default suits general housing. For fixed equipment that can run at full power for long periods, such as a cooktop, an electric shower or a hot water system, a cautious approach is to use 1.0, so the calculation does not understate the demand. Lowering the factor reduces the calculated current, but it only makes sense where the usage pattern genuinely supports it.
Breaker ratings and what they protect
Miniature circuit breakers are made in a standard series of ratings. The preferred values in IEC 60898-1 are 6, 10, 16, 20, 25, 32, 40, 50 and 63 A. Choose the next rating above the calculated current. A load of 9.5 A needs a 10 A breaker, and a load of 17.3 A needs a 20 A breaker.
The breaker curve matters as well as the rating. Curve B breakers trip at a lower multiple of their rating and suit resistive loads and lighting. Curve C breakers tolerate the short, high starting current of motors and compressors, which is why they are usually the better choice for air conditioners, heat pumps and washing machines.
Take a bedroom in a weatherboard house in Auckland with a 1,500 W heat pump, a 200 W television, a 100 W computer and 60 W of LED lighting. That is 1,860 W installed. At a factor of 0.8 the simultaneous load is 1,488 W, or about 7.2 A at 230 V with a power factor of 0.9. A 10 A breaker suits that circuit, provided the cable is sized to match, and a C curve breaker is preferred because of the heat pump's starting current.
Cable size: the rule that is easy to miss
The cable cannot be chosen independently of the breaker. The breaker exists to protect the cable, so the cable must be able to carry the breaker's rated current continuously without overheating. Its current-carrying capacity depends on the conductor size, the insulation, how it is installed (for example, clipped to a surface or enclosed in a wall), how many cables are grouped together and the ambient temperature. These values come from the tables in AS/NZS 3000:2018, not from a single figure, so this calculator gives a suggested size to check rather than a final design.
If the breaker is rated higher than the cable can carry, the breaker may not trip before the cable overheats, and it gives no real protection for the cable at that point. That is the main reason an installation should never be fixed by fitting a larger breaker to a circuit that keeps tripping.
Common mistakes in domestic installations
Running a heat pump from a general power point. Air conditioners and heat pumps usually need their own dedicated circuit, with protection and cable sized for their rating. Sharing a general circuit with a heater or kettle can push the total current beyond what the circuit was designed to carry.
Using extension leads as a permanent solution. Extension leads are designed for occasional use. A heavy load run through one for months or years heats the lead, its plugs and its sockets, and the insulation degrades gradually. The problem is not immediate, but the fire risk grows over time.
Ignoring starting current. Motors in washing machines, compressors in fridges and heat pumps draw a starting current several times their running current for a short moment. A C curve breaker tolerates these peaks. A B curve breaker can trip even when the continuous current is well within its rating.
Confusing heating or cooling capacity with electrical input. Heat pumps are often sold by their heating or cooling output in kilowatts, which is not the same as the electrical power they draw. Enter the electrical input figure from the rating plate into the calculator, not the output figure from the brochure.
When not to use this calculator
The calculator is written for single-phase domestic circuits. It is not suitable for three-phase supplies, commercial or industrial installations, or specialist loads that have their own installation requirements, such as electric vehicle chargers and large battery systems. For those, the manufacturer's instructions and the relevant standards take priority.
A few edge cases are worth knowing. A zero load gives a zero current. A zero or negative power value is not meaningful and should be corrected before the result is read. A simultaneity factor of 1.0 gives the worst-case result for the installed load, which makes it a useful check for equipment that may run flat out.
When to call a registered electrician
The calculator estimates loads and shows whether an existing circuit is likely to sit within reasonable limits. It does not confirm that an installation is safe. Work on fixed wiring, the switchboard or new circuits should be carried out by a registered electrician, who issues a Certificate of Compliance for the work. WorkSafe New Zealand is the regulator for electrical safety and publishes useful guidance on electrical work in homes. The main technical reference for domestic wiring is AS/NZS 3000:2018, the Wiring Rules.
If a breaker trips repeatedly, a switch or socket feels warm, or a cable smells of burning, switch the circuit off and have it inspected. Do not replace the breaker with a larger one to stop the trips, because that removes the protection the cable depends on.
Frequently asked questions
What is the maximum load on a standard power point in New Zealand?
The power point is only as capable as the circuit behind it, so the practical limit is set by the breaker and cable of that circuit rather than by the socket alone. At 230 V, a circuit protected at 16 A can carry 3,680 W of purely resistive load (16 × 230). Using the calculator's planning power factor of 0.9, that becomes about 3,312 W. Appliances with large loads, such as an electric cooktop or a hot water system, normally need their own circuit. A 6,000 W heater plugged into a general power point would draw about 26 A, so it would trip the breaker often and keep the cable under heavy load.
What breaker should I use for a bedroom with an air conditioner?
It depends on the electrical input of the unit, which is shown on its rating plate. Take a 1,500 W heat pump, a 200 W television and 80 W of lighting. At a simultaneity factor of 0.8 the simultaneous load is 1,424 W, or about 6.9 A at 230 V with a power factor of 0.9, which points to a 10 A breaker. If the same room also has a 2,000 W convector heater, the simultaneous load reaches about 3,024 W (14.6 A), and the next rating up is 16 A. Air conditioners have a high starting current, so a C curve breaker is usually the better choice, and an electrician should confirm the cable size for the chosen rating.
What is the simultaneity factor, and when should I change it?
The simultaneity factor is the share of installed power that runs at the same time. A room with 3,000 W installed and a factor of 0.8 has a simultaneous demand of 2,400 W. A lower factor reduces the calculated current and therefore the breaker needed, so it should only be used where the way the room is used supports it. The 0.8 default suits general housing. For fixed equipment that may run at full power for long periods, such as an electric cooktop, an electric shower or a hot water system, use 1.0 so the result does not understate the demand. The factor is a planning assumption, so confirm the design method for your installation against AS/NZS 3000:2018.
What cable size should I use on a general power point circuit?
The breaker alone does not decide the cable size. The cable must carry the breaker's rated current continuously without overheating, and its current-carrying capacity depends on the conductor size, insulation, installation method, grouping and ambient temperature. Those values come from the tables in AS/NZS 3000:2018, so the right size depends on how the cable is run. A breaker rated above the cable's capacity can let the cable overheat before the breaker trips. This calculator gives a suggested size to check, but a registered electrician should confirm it against the actual installation before any work is done.
Can I add more appliances to an existing circuit?
Yes, if the total current stays within the breaker rating and the cable is suitable for it. At 230 V and the 0.9 planning power factor, a 16 A circuit has a planning capacity of about 3,312 W. If it already feeds 2,000 W of appliances, that leaves roughly 1,300 W of headroom on the planning figure. That margin is not a guarantee. Motors with high starting currents, such as air conditioners and washing machines, can trip a breaker even when the running current is within its limit, and a load that stays close to the limit keeps the cable warm. Any change to a fixed circuit should be checked by a registered electrician.
When do I need a registered electrician in New Zealand?
Work on fixed wiring, the switchboard or new circuits should be carried out by a registered electrician, who issues a Certificate of Compliance for the work. The calculator is a planning tool. It estimates the load and shows whether an existing circuit is likely to sit within reasonable limits, but it cannot confirm that an installation is safe. WorkSafe New Zealand is the regulator for electrical safety and publishes guidance on electrical work in homes. If a breaker trips repeatedly or a socket feels hot, switch the circuit off and have it checked, rather than fitting a larger breaker.
View all Renovation & Systems calculators →
By RivoCalc · Reviewed under our editorial methodology · Updated 12 May 2026
This calculator gives an estimate for planning only. Real loads vary with the equipment, how it is used and the wiring of the building, so the results are not a substitute for design, installation or testing by a registered electrician under AS/NZS 3000:2018. Confirm breaker and cable sizes with a registered electrician before any work begins.