Room Electrical Load and Breaker Calculator

Calculates the simultaneous load, current, breaker rating and cable size guidance for each room of a Singapore home at 230 V.

A bedroom with a 1,500 W air-conditioner, a 200 W television and two 60 W chargers has 1,820 W installed. With a simultaneity factor of 0.8, the load running at the same time is 1,456 W, which draws about 7.0 A at 230 V with a power factor of 0.9. The next standard breaker rating above 7.0 A is 10 A, and that is the figure this calculator returns for that room.

Most homes in Singapore, from a 4-room HDB flat in Tampines to a condominium in Bukit Timah, are supplied at 230 V single-phase. Load planning matters most during a renovation, when a new air-conditioner, a second computer or an instantaneous water heater is added to a room that was wired for a lighter load. A circuit that was adequate before can start tripping under normal use once the new equipment runs at the same time as the old.

The calculator adds the rated power of everything fixed to a room, including lighting, socket-outlet appliances and any heating or cooling system. The simultaneity factor reduces that total to the load likely to run at the same time, and the current follows from the formula explained below. Using the same bedroom, adding a 300 W computer raises the simultaneous load to 1,696 W, or about 8.2 A. That still fits within a 10 A breaker, but the margin narrows and the cable should be checked again before the change.

The result is a planning estimate, not a certificate. It gives the simultaneous power, the current, the breaker rating and cable size guidance for each room, but it does not replace the design of a licensed electrical worker. That design should be checked against SS 638, the Singapore code of practice for electrical installations.

The result updates automatically.

Selecting the type fills in typical values — adjust as needed.

Total of the light fittings installed. LED: 5–15 W/fitting; halogen: 35–50 W/fitting.

TV (~100 W), computer (~80 W), games console (~150 W), chargers, etc.

Air conditioning (~1,000–3,500 W), convector heater (~1,000–2,000 W), electric towel rail (~200–600 W).

Electric cooker (~6,000–7,000 W), oven (~2,000–3,500 W), washing machine (~2,000 W).

The percentage of appliances running at the same time. 80% is the typical value for a home.

Recommended breaker

10 A

Minimum rating for a current of 7.3 A

Simultaneous load

1,504 W

80% of 1,880 W installed

Total installed load
1,880 W
Lighting
80 W
Appliances / sockets
300 W
Heating / AC
1,500 W
Other appliances
0 W
Circuit current
7.3 A
Minimum cable size
1,5 mm²

Turn this calculation into a quote for your client

We're building a tool for professionals. Be among the first to try it.

Share

How it works

1

Select the room type. Typical loads fill in automatically.

2

Adjust the lighting power to the sum of the lamps installed or planned.

3

Enter the power of socket-outlet appliances and of any heating or cooling system.

Formula

I = (P_inst × sf) / (V × 0,9)
I — Current in the circuit (A)
P_inst — Total installed power (W) = lighting + socket-outlet appliances + heating or cooling systems + other fixed loads
sf — Simultaneity factor (decimal), typically 0.80 for housing
V — Single-phase supply voltage in Singapore (V): 230 V
0,9 — Power factor (cos φ) of 0.9, shown with a decimal comma as in the formula, assumed for typical domestic loads

How the calculation works

How to calculate the electrical load per room

Sizing an electrical circuit involves three variables: the installed load, the simultaneity factor and the supply voltage. Get any one of them wrong and the circuit ends up either undersized, tripping during normal use, or oversized, allowing more current than its cable can safely carry. The second error is the more dangerous one, because the breaker does not act until the cable has already overheated.

Singapore's domestic supply is 230 V single-phase, with 400 V three-phase supplies for larger loads, as set out in SS 638. The calculator uses 230 V for every room. The power factor of 0.9 is a simplifying assumption that stands in for a mix of resistive and motor-driven loads, and it is discussed further below.

The formula and the simultaneity factor

The current in a single-phase circuit follows from the active power, the voltage and the power factor: current equals power divided by the product of voltage and power factor. The calculator applies this to the simultaneous power, not to the total of every appliance in the room. Simultaneous power is the power of the equipment that runs at the same time.

The simultaneity factor bridges the two. A room with 2,000 W installed and a factor of 0.8 has 1,600 W of simultaneous load. At 230 V and a power factor of 0.9, that is 1,600 divided by 207, or about 7.7 A. The result, not the installed total, is what determines the breaker.

In the formula, the power factor appears as 0,9, with a decimal comma. It means the same 0.9 used everywhere else on this page.

The calculator defaults to 0.8 for housing, which is a practical starting point for general living areas. Some situations call for a higher value. Fixed appliances such as electric hobs, ovens, washing machines and instantaneous water heaters can run at full power for long periods. Because the default assumes that only part of the connected load runs at once, a factor of 1.0 is the more cautious setting for these appliances. A lower factor is harder to justify for a room where several appliances are often used at once, such as a home office with a computer, monitor, printer and charger.

Miniature circuit breaker ratings

Miniature circuit breakers follow the IEC 60898 series, and the standard ratings are 6, 10, 16, 20, 25, 32, 40, 50 and 63 A. The breaker is the next rating above the calculated current. A circuit with a calculated current of 9.5 A therefore takes a 10 A breaker, and a circuit at 17.3 A needs at least a 20 A breaker. Choosing a rating just above the calculated current keeps the protection close to the load without causing nuisance tripping.

Breaker curves matter as well. Curve B breakers suit resistive loads and lighting. Curve C breakers tolerate the short starting current of motors, compressors and equipment such as air-conditioners and washing machines. A curve B breaker on a motor-driven circuit can trip even when the running current is within the rating, because the starting current is several times higher than the running current.

Cable size: the rule many people overlook

The cable is not independent of the breaker. The breaker protects the cable only if it trips before the cable overheats, which requires the cable's current-carrying capacity to be at least the breaker rating. Protecting a cable with a breaker rated above its capacity removes the protection in practice, because the breaker will not trip before the cable reaches a dangerous temperature.

The current-carrying capacity depends on the conductor size, the insulation, the number of cables grouped together and the way the cable is installed, whether clipped to a surface, run in conduit or buried in a wall. This calculator gives the cable size as guidance only. The precise selection should follow the cable rules in SS 638 and the installation conditions on site.

Common mistakes in home wiring

Connecting a split-unit air-conditioner to a general-purpose socket circuit is a frequent error. The unit's rated current, added to the other appliances on the same circuit, can exceed what that circuit was designed for, and its starting current adds a further peak. Check the rating plate on the unit and have a licensed electrical worker confirm whether it needs its own circuit and protection.

Extension leads are another common source of trouble. They are designed for occasional use, not for permanent connection at full load. When a heater or cooker runs from an extension lead for weeks, heat builds up in the lead and the plug, and the insulation ages faster than the user notices. The safe answer is a proper socket outlet on a circuit sized for the load.

Ignoring starting current is the third mistake. Motor-driven appliances such as refrigerators, air-conditioners and washing machines draw a starting current several times their running current for a short time. Breaker curve and rating must be chosen with that in mind, not only from the nameplate running current.

Edge cases and limits of the result

If the installed power is zero, the simultaneous load and the current are also zero, and no breaker is needed. A simultaneity factor above 1.0 has no physical meaning, because a room cannot draw more than its installed power. When the calculated current is above 63 A, the result is outside the standard breaker list used here, and the installation needs a separate design by a licensed electrical worker.

Results close to a breaker boundary deserve attention. A calculated current of 10.1 A, for example, moves the breaker from 10 A to 16 A, so a small change in the equipment list can change the rating. Recalculate after every addition rather than assuming the existing rating still holds.

The current depends on the power factor. If the real power factor of a room's equipment is below 0.9, the current for the same power is higher than the calculator shows, because the current is the power divided by the voltage and the power factor. The calculator does not measure the power factor of an installation.

Reading the result

The calculator returns four figures for each room: the simultaneous power in watts, the current in amperes, the breaker rating and the cable size guidance. Read them in that order. The current links the first figure to the rest, because the breaker and the cable both follow from it.

When to use the calculator and when not to

Use the calculator to estimate loads during planning, to check whether an existing circuit has room for another appliance, or to understand why a breaker keeps tripping. It is useful for comparing options, such as whether a new air-conditioner can share a circuit with the lighting or needs its own.

Do not use it as the sole basis for installation work. It does not account for the length and route of individual cable runs, for voltage drop over long distances, for the way loads are shared across a distribution board, or for the specific requirements of the building. It also does not replace the inspection and testing of an existing installation.

Working with a licensed electrical worker

Electrical installation work is best left to a licensed electrical worker. Adding circuits, changing a distribution board or altering cable sizes are tasks for a licensed professional. The worker should check the design against SS 638, confirm the cable and breaker selection for each circuit, and record the results.

A useful way to prepare is to note the rated power of every appliance in each room, the planned use of the room and the layout of the existing distribution board. With those figures, the calculator gives a fast estimate, and the licensed electrical worker can confirm the final design on site.

Frequently asked questions

What is the maximum load on a socket outlet in a Singapore home?

The circuit sets the real limit, because a socket outlet can only deliver what the breaker and cable behind it allow. High-power appliances such as instantaneous water heaters and electric hobs are usually best served by a dedicated circuit, and a licensed electrical worker should confirm the rating and the cable before connection. Plugging a high-power cooker into a general-purpose socket leads to repeated tripping and heating of the cable and plug. The calculator is for planning the load on each circuit, not for selecting the rating of a single outlet.

Which breaker should a bedroom with an air-conditioner use?

It depends on the rated power of the air-conditioner. For a bedroom with a 1,500 W air-conditioner, a 100 W television and 80 W of lighting, the total installed power is 1,680 W. With a simultaneity factor of 0.8 and a power factor of 0.9, the current is about 6.5 A, so the next standard rating, 10 A, applies. Adding a 2,000 W heater brings the current to about 14.2 A, which needs a 16 A breaker. The final choice depends on the unit's nameplate and the requirements of SS 638, so confirm it with a licensed electrical worker before installation.

What is the simultaneity factor and how does it affect sizing?

The simultaneity factor is the share of installed appliances that run at the same time. A room with 3,000 W installed and a factor of 0.8 needs to plan for 2,400 W running together. This reduces the calculated current and therefore the breaker and cable sizes. The calculator defaults to 0.8 for housing. For fixed appliances that can run at full power for long periods, such as an instantaneous water heater, a factor of 1.0 is the more cautious choice, because those appliances can draw their full rating continuously.

Which cable size should a general-purpose socket circuit use?

The cable must be able to carry at least the current rating of the breaker that protects it. A breaker rated above the cable's current-carrying capacity offers no protection against overheating, because it will not trip before the cable reaches a dangerous temperature. The exact size depends on the cable type, how it is installed (clipped to a surface, in conduit or buried in a wall) and the cable selection rules in SS 638. Use the calculator's result as a starting point and have the final cable size confirmed by a licensed electrical worker.

Why does the calculator use a power factor of 0.9?

The power factor describes how much of the current in an AC circuit does useful work. Its real value depends on the appliances in each room, and this calculator does not measure it. The value of 0.9 is a simplifying assumption for mixed household loads. If the real power factor of a room's equipment is lower, the current for the same power is higher than the calculator shows, because the current is the power divided by the voltage and the power factor. The value should not be used for industrial or commercial design.

When must a licensed electrical worker be engaged in Singapore?

Work on fixed electrical installations, such as adding new circuits, changing a distribution board or upgrading cable sizes, is normally work for a licensed electrical worker, and the design should be checked against SS 638. Replacing a single socket outlet or switch may be a smaller task, but it is safest to check the scope with a licensed contractor first. This calculator estimates loads only. It does not certify any installation and does not replace a design by a qualified professional.

Related calculators

View all Renovation & Systems calculators →

By RivoCalc · Reviewed under our editorial methodology · Updated 12 May 2026

The results are estimates for planning only. Real demand varies with the appliances you choose, how you use them and the local conditions, so the figures will not match every household. Electrical installation work should be carried out by a licensed electrical worker, and the final design should be checked against SS 638.